Air Velocity Transducer TSI Model 8475
Features
Accuracy: +3.0% of reading2,
2From 68 to 78.8°F (20 to 26°C), outside this range and within temperature compensation
range add 0.28% per °F (0.5% per °C). Directional sensitivity of the Model 8475 is +5%/-20% of reading +0/-10 ft/min
(+0/-0.05 m/s) over 270° solid angle regardless of flow direction.
+1.0% of full scale of selected range
Field selectable range:
10 ft/min to 100, 125, 150, 200, 250, 300, 400, 500 ft/min (0.05 m/s to 0.5,
0.75, 1.0,1.25, 1.50, 2.0, 2.5 m/s)
Response to flow: 5 sec5,
5For 63% of final value, tested at 500 fpm (2.5 m/s)
Temperature range:
Compensation: 32 to 140°F (0 to 60°C)
Operating (electronics): 32 to 200°F (0 to 93°C)
Operating (sensor): 32 to 200°F (0 to 93°C)
Storage: 32 to 200°F (0 to 93°C)
Resolution (minimum): 0.07% of selected full scale
Input power: 11 to 30 VDC or 18 to 38 VAC, 350 mA max6
6Input voltage must be maintained within specifications at the transducer
Output:
Impedance: Voltage mode: less than 1 ohm, 20mA
max source current
Resistance: Current mode: 500 ohms maximum load
Signal: Field selectable 0 to 5V, 0 to 10V,
0 to 20, 2 to 10V, mA, 4 to 20 mA
Time constant: Field selectable 0.05 to 10 seconds
Probe length: 3 in., 6 in., 9 in., 12 in. (7.5 cm, 15 cm, 22.5 cm, or 30 cm)
All models contain on-board electronics and calibration curves that provide a linear signal output. This linear signal is sent out as either a current (mA) or a voltage (V) signal, allowing output to a variety of data loggers or data acquisition systems. In addition, the current and voltage output ranges are user-selectable for your convenience.