Micromanometer DP-CALC TSI Model 5815
. Measure differential and static pressure from -15 to 15 in.
.H2O (-3735 to +3735 Pa).
. Calculate and display velocity when using a Pitot tube.
Product Specifications
Static/Differential Pressure:
Range1: -15 to +15 in. H2O
(-28.0 to 28.0 mm Hg, -3735 to + 3735 Pa)
Accuracy: +1% of reading +0.005 in. H2O
+0.01 mm, +1 Pa
Resolution: +0.001 in. H2O (0.1 Pa, 0.01 mm Hg)
Velocity (Pitot tube):
Range2: 250 to 15,000 ft/min (1.27 to 78.7 m/s)
Accuracy3: +1.5 at 2,000 ft/min (10.16 m/s)
Resolution: 1 ft/min (0.1 m/s)
Instrument Temperature Range:
Operating: 40 to 113°F (5 to 45°C)
Storage: -4 to 140°F (5 to 45°C)
External Meter Dimensions:
3.3 in. x 7.0 in. x 1.8 in. (8.4 x 17.8 x 4.4 cm)
Meter Weight with Batteries:
0.6 lbs. (0.27 kg)
Power Requirements:
Four AA-size batteries
1Overpressure range = 190 in. H2O (7 psi, 360 mmHg, 48 kPa).
2Pressure velocity measurements are not recommended below 1,000 ft/min (5 m/s).
3Accuracy is a function of converting pressure to velocity. Conversion accuracy improves when actual pressure values increase.
Services
. First level maintenance and repair work performed by Aerometrik.
. Taking charge of and monitoring the metrology of this equipment with TSI.
You may also like…
-
Accubalance Air Capture Hood TSI Model 8380
. Accurately measures pressure, velocity and flow to help you meet industry standards
. Auto-zeroingpressure sensor reduces user-steps and saves time
. Automatic density correction increases reading accuracy
. Intuitive menu structure allows for ease of use and setup
. Large graphic display with backlight offers easy-to-use interface
– Displays up to five measurements simultaneously
– On-screen messages and instructions
– Programmed for multiple languages
. Integrated Log-Tchebycheff duct traverse application simplifies calculations
. Bluetooth communications for transferring data or remote polling
. Includes downloading software with USB cable
. Accommodates optional pitot, air flow (straight pitot),
temperature/relative humidity, velocity matrix, or thermoanemometer probes for use in multiple applications -
Air Velocity Meters VELOCICALC TSI 9535
. Simultaneously measure temperature and velocity
. Displays up to three measurements simultaneously
. Calculates volumetric flow and actual/standard velocity
. Data log 12,700+ samples and 100 test IDs
. LogDat2TM downloading software included
. Articulated probe versions available (9535-A) -
VelociCalc Multi-Function Ventilation Meter TSI 9565
. Straight Air Velocity Probe 964 measure air velocity, temperature and relative humidity
. Includes differential pressure sensor
. Best-in-class air velocity accuracy
. Optional “smart” plug-in probes, including VOC, CO2, and rotating vane probes
. Accommodates up to two K-alloy thermocouples
. Large graphic display
. Displays up to five measurements simultaneously
. On-screen messages and instructions
. Program for local language
. Intuitive menu structure allows for ease of use and setup
. Multiple data logging formats
. Bluetooth communications for transferring data or remote polling
. Includes TrakPro™ and LogDat2™ downloading software with USB cable